Table. Checking the refrigerant pressure.
| Malfunction | Symptoms | Possible cause of the malfunction | Troubleshooting methods. |
| Outlet pressure (high pressure line) above normal | After turning off the compressor, the pressure is about 196 kPa, then gradually decreases | Air in the air conditioning system | Remove refrigerant from the system, evacuate and recharge the air conditioning system |
| When cooling the condenser with water, there are no bubbles in the service window | Excess refrigerant in the air conditioning system | Remove refrigerant from the system, evacuate and recharge the air conditioning system | |
| Not enough air passes through the condenser or no air passes through at all | -The radiator or condenser is clogged with dirt -The condenser fan or cooling system fan is faulty | -Remove dirt -Check voltage and fan speed -Check control circuit | |
| Condenser tubes become excessively hot | Low refrigerant pressure in the air conditioning system | - | |
| Outlet pressure (high pressure line) below normal | Excessive amount of bubbles in the service window, the condenser is not hot | Lack of refrigerant in the air conditioning system | - Check the system for leaks - Charge the system |
| -After the compressor is turned off, the pressure in the high and low pressure lines quickly equalizes -The pressure in the low pressure line is higher than normal | - Bypass valve malfunction - O-ring seal | Replace the compressor | |
| No cooling at the expansion valve outlet, low pressure line gauge shows vacuum | - Expansion valve malfunction - Moisture in the system | -Replace the expansion valve -Remove the refrigerant from the system, evacuate and charge the air conditioning system | |
| Inlet pressure (low pressure line) below normal | Excessive amount of bubbles in the service window, the condenser is not hot | Lack of refrigerant in the air conditioning system | -Check the system for leaks -Charge the system |
| No cooling at the expansion valve outlet, low pressure line tubes are warm, low pressure line gauge shows vacuum | - Expansion valve malfunction - Expansion valve freezing (moisture in the system) | -Replace the expansion valve -Remove the refrigerant from the system, evacuate and charge the air conditioning system | |
| - Low air temperature at the outlet - Weak air flow coming out of the deflectors | Evaporator freezing | - Check the air temperature sensor behind the evaporator | |
| Expansion valve freezing | Clogged expansion valve | Clean or replace the expansion valve | |
| Inlet pressure (low pressure line) above normal | Low pressure line hoses are colder than the evaporator | The expansion valve has been open for too long | Repair or replace the expansion valve |
| When the condenser is cooled by water, the pressure at the inlet decreases | Excess refrigerant in the air conditioning system | Remove refrigerant from the system, evacuate and recharge the air conditioning system | |
| After the compressor is turned off, the pressure in the high and low pressure lines quickly equalizes | -High pressure valve malfunction -High pressure valve clogged | Replace the compressor |